Wireless Differential Pressure Transmitter

The ADDA-P-WX wireless differential pressure transmitter is developed for pressure and level monitoring in smart petroleum, smart water, smart gas, smart heating, and smart fire protection applications. It uses low-power wireless communication, requires no wiring, supports local or remote parameter setting, and provides IP67 sealed waterproof protection.

Authoritative Qualification Certifications

We hold ISO quality certification, national high-tech enterprise qualification, China measuring instrument type approval, and explosion-proof and safety certifications to support reliable product quality.

Custom Engineering

Configurable materials, connections, signals, displays, and installation solutions for different process environments.

Wireless Differential Pressure Transmitter

Product Overview

The ADDA-P-WX wireless differential pressure transmitter uses monocrystalline silicon piezoresistive sensing technology. This high-stability, high-reliability wireless instrument is suitable for pressure and level monitoring in smart petroleum, smart water, smart gas, smart heating, and smart fire protection applications. It uses ultra-low-power wireless communication and requires no signal wiring, enabling convenient installation.

Applications

1. Smart petroleum    2. Smart water

3. Smart gas    4. Smart heating

5. Smart fire protection

Product Features

Protection Grade: IP67, sealed waterproof design

Supports parameter configuration using local buttons or a remote device.

5-digit segmented LCD with a -30~70 degrees C operating temperature range. Displays pressure, battery level, wireless parameters, and other information.

Adjustable installation direction: connects to the field pipeline valve through a union or adapter, allowing the direction to be adjusted.

19Ah high-energy lithium thionyl chloride battery for long service life; optional battery and external power supply configuration.

High-gain antenna with a maximum wireless transmission distance of 2000m.

Supports private clouds and the matching cloud platform. Supports sending data to a specified IP address or website.

Ultra-low power consumption and a WDT watchdog design support stable long-term operation. Upper and lower alarm limits and dynamic-change thresholds can be configured; alarm information is reported immediately.

Supports data access through a mobile app and data reading by OPC configuration software.

Technical Specifications

Communication MethodZigbee

(SZ9/A11)

LoRaLoRaWANNB-IOT4G
Parameter ConfigurationLocalLocalLocalRemoteRemote
Power SupplyLithium thionyl chloride battery (capacity: 19Ah); default sampling interval: 3 seconds
Data Interval (minutes)51206060
Battery Life3 years3 years4 years2 years3 years
Measuring Mediumliquids, gases
Operating ModeScheduled data transmission with an adjustable transmission interval.
Threshold SettingsConfigurable pressure upper and lower limits and dynamic-change thresholds.
Measuring Range-0.1~40MPa
Accuracy Class0.1 class (default 0.25%F.S.; 0.1 and 0.2 accuracy classes can be customized)
Overload PressureSee the range specifications.
Process Connection1/4NPT female thread (other connections can be customized)
Temperature Compensation-20~70 degrees C
Operating EnvironmentTemperature: -30 degrees C~70 degrees C; humidity: <93%RH
Housing MaterialCast aluminum
Protection GradeIP67

 

Pressure TypeDifferential PressureGauge PressureAbsolute Pressure
Range50Pa-10MPa200Pa-40MPa2kPa-10MPa
Output SignalZigbee(SZ9/A11), LoRa, LoRaWAN, NB-IOT, 4G
Reference Accuracy±0.075% Upper Range Limit, optional ±0.05% Upper Range Limit, see specifications for details±0.15% Upper Range Limit, optional ±0.1% Upper Range Limit, see specifications for details

 

Differential Pressure Range
Nominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Static Pressure RangeHigh-Side OverloadLow-Side Overload
6kPa50Pa-6kPa6kPa25MPa25MPa16MPa
40kPa400Pa-40kPa40kPa40MPa25MPa16MPa
250kPa2.5kPa-250kPa250kPa40MPa25MPa500kPa
1MPa10kPa-500kPa1MPa40MPa25MPa500kPa
3MPa30kPa-500kPa3MPa40MPa25MPa500kPa
10MPa100kPa-500kPa10MPa40MPa25MPa500kPa
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits

|URV-LRV | ≥ Minimum Range

 

Gauge Pressure Range
Nominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Overload
6kPa50Pa-6kPa6kPa25MPa
40kPa400Pa-40kPa40kPa25MPa
250kPa2.5kPa-100kPa250kPa25MPa
1MPa10kPa-100kPa1MPa25MPa
3MPa30kPa-100kPa3MPa25MPa
10MPa100kPa-100kPa10MPa25MPa
40MPa400kPa-100kPa40MPa42MPa
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits

|URV-LRV | ≥ Minimum Range

 

Absolute Pressure Range
Nominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Overload
40kPa2kPa0kPa40kPa500kPa
250kPa12.5kPa0kPa250kPa4MPa
1MPa50kPa0kPa1MPa6MPa
3MPa150kPa0kPa3MPa10MPa
10MPa500kPa0kPa10MPa20MPa
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits

|URV-LRV | ≥ Minimum Range

Accuracy
Based on standards and reference test conditions, including best fit straight line (BFSL), hysteresis, repeatability. Calibration temperature: 20 degrees C ±5 degrees C .
Linear Output AccuracyD/GTD<=5±0.1%Span6kPa, 40kPa, 250kPa, 1MPa, 3MPa, 10MPa, 40MPa
TD>5±(0.002+0.025TD) % Span
ATD<=5±0.2% Span40kPa
±0.1% Span250kPa, 1MPa, 10MPa
TD>5±(0.005+0.04TD) % Span40kPa
±(0.005+0.025TD) % Span250kPa, 1MPa, 10MPa
Note: TD (Turn down) means turndown ratio, TD= maximum range / current range.

 

Ambient Temperature Influence
6kPa± (0.1+0.005TD)%/20 degrees C of Span
40kPa , 250kPa, 1MPa, 3MPa, 10MPa± (0.075+0.005TD)%/20 degrees C of Span

 

Environmental Conditions
ItemCondition
Operating Ambient Temperature Range-40 degrees C ~ 85 degrees C, LCD display: -30 degrees C ~ 70 degrees C
Storage Ambient Temperature Range-40 degrees C ~ 100 degrees C, LCD display: -40 degrees C ~ 85 degrees C
Measured Medium Temperature RangeSilicone oil filling: -40 degrees C ~ 85 degrees C
Inert filling liquid: -20 degrees C ~ 80 degrees C
Operating Ambient Humidity Range5%RH~93%RH@40 degrees C
Hazardous AreaPCECCertificate No.: CE23.2876X

Ex db IIC T6 Gb

Ex tb IIIC T80 degrees C Db

 

Related Products

Case Showcase

Frequently Asked Questions

Find quick answers about product selection, customization, technical parameters, delivery, and support for ADDA industrial measurement instruments.

官网询盘

Please provide the measured medium, measuring range, process temperature, process pressure, connection type, output signal, power supply, installation environment, and communication method if remote monitoring is required.

Yes. ADDA can provide customized solutions based on measuring range, process connection, wetted material, display type, communication protocol, installation method, and working environment.

Many ADDA instruments are available with explosion-proof or intrinsically safe configurations. Please confirm the site classification and certification requirements before selection.

Yes. Our team can help recommend a suitable instrument configuration after reviewing your application conditions, including medium, range, connection, output signal, and installation requirements.

Lead time depends on product type, quantity, customization requirements, and certification needs. Standard products usually have a shorter delivery time, while customized models may require additional production time.