Smart Pressure Transmitter

The ADDA-P Series smart pressure transmitter uses diffused silicon, ceramic piezoresistive, or ceramic capacitive sensing technology for pressure and level measurement. An embedded signal processing module provides static pressure and temperature compensation. Available measuring ranges, protection ratings, and output options depend on the selected configuration.

Authoritative Qualification Certifications

We hold ISO quality certification, national high-tech enterprise qualification, China measuring instrument type approval, and explosion-proof and safety certifications to support reliable product quality.

Custom Engineering

Configurable materials, connections, signals, displays, and installation solutions for different process environments.

Product Features

The ADDA-P Series uses diffused silicon, ceramic piezoresistive, or ceramic capacitive sensor technology. The sensor chips are manufactured using advanced processes to provide high accuracy, high overpressure resistance, and stable performance. An embedded signal processing module combines static pressure and temperature compensation to maintain measurement accuracy and long-term stability across a wide range of pressure and temperature conditions.

  • Stable performance with accuracy up to 0.1%F.S.
  • Turndown ratio up to 5 : 1.
  • A high-performance EMC protection circuit module reduces the influence of electromagnetic interference on the output.
  • High stability: ±0.1% Span/year.

Applications

Pressure and level measurement.

Measuring Medium

Media compatible with the wetted materials.

Performance Specifications

Accuracy±0.1%, ±0.2%, 0.5% Upper Range Limit,  see specifications for details
Range10kPa~100MPa, see selection table for details
Annual Stability±0.1% Span/year
Ambient Temperature Influencesee specifications for details
Voltage InfluenceWhen the supply voltage varies within 10.5V/16.5V~36V DC, changes in zero point and span shall not exceed ±0.001%URL/V
Mounting Position InfluenceTransmitter installation may cause zero error, this error can be corrected by zero adjustment, with no effect on accuracy
Vibration InfluenceTested according to GB/T18271.3/IEC61298-3 test, < 0.1%
Output Signal4mA~20mADC+HART

Modbus-RTU/RS485

Protection GradeIP65/IP67/IP68

 

Range (ADDA-P-1J-K)

Pressure TypeNominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Overload
G/N20kPa5kPa-20kPa20kPa1.5 times the nominal range
35kPa10kPa-35kPa35kPa1.5 times the nominal range
80kPa16kPa-80kPa80 kPa1.5 times the nominal range
150kPa30kPa-100kPa150kPa1.5 times the nominal range
300kPa60kPa-100kPa300 kPa1.5 times the nominal range
700kPa140kPa-100kPa700 kPa1.5 times the nominal range
1.3MPa260kPa-0.1MPa1.3MPa1.5 times the nominal range
2.5MPa500kPa-0.1MPa2.5MPa1.5 times the nominal range
4MPa800kPa-0.1MPa4MPa1.5 times the nominal range
10MPa2MPa-0.1MPa10MPa1.5 times the nominal range
25MPa5MPa-0.1MPa25MPa1.5 times the nominal range
40MPa8MPa-0.1MPa40MPa1.5 times the nominal range
60MPa12MPa-0.1MPa60MPa1.5 times the nominal range
100MPa20MPa-0.1MPa10MPa1.5 times the nominal range
A35kPa10kPa0kPa35kPa105kPa
80kPa16kPa0kPa80kPa1.5 times the nominal range
150kPa30kPa0kPa150kPa1.5 times the nominal range
300kPa60kPa0kPa300kPa1.5 times the nominal range
700kPa140kPa0kPa700kPa1.5 times the nominal range
1.3MPa260kPa0kPa1.3MPa1.5 times the nominal range
2.5MPa500kPa0kPa2.5MPa1.5 times the nominal range
4MPa800kPa0kPa4MPa1.5 times the nominal range
10MPa2MPa0kPa10MPa1.5 times the nominal range
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits, |URV-LRV|≥ Minimum Range

Range (ADDA-P-1J-B)

Pressure TypeNominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Overload
G/N50kPa10kPa0kPa50kPa2 times the nominal range
100kPa20kPa-100kPa100kPa2 times the nominal range
200kPa40kPa-100kPa200kPa2 times the nominal range
500kPa100kPa-100kPa500kPa2 times the nominal range
1MPa200kPa-0.1MPa1MPa1.5 times the nominal range
2MPa400kPa-0.1MPa2MPa3.5MPa
5MPa1MPa-0.1MPa5MPa10MPa
10MPa2MPa-0.1MPa10MPa15MPa
20MPa4MPa-0.1MPa20MPa30MPa
40MPa8MPa-0.1MPa40MPa50MPa
60MPa12MPa-0.1MPa60MPa75MPa
A100kPa20kPa0kPa100kPa2 times the nominal range
200kPa40kPa0kPa200kPa2 times the nominal range
500kPa100kPa0kPa500kPa2 times the nominal range
1MPa200kPa0kPa1MPa1.5 times the nominal range
2MPa400kPa0kPa2MPa3.5MPa
5MPa1MPa0kPa5MPa10MPa
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits, |URV-LRV|≥ Minimum Range

Range (ADDA-P-1J-C)

Pressure TypeNominal RangeMinimum RangeLower Range Limit (LRL)Upper Range Limit (URL)Overload
G/N10kPa2kPa-10kPa10kPa400kPa
20kPa5kPa-20kPa20kPa600kPa
50kPa10kPa-50kPa50kPa600kPa
100kPa20kPa-100kPa100kPa1MPa
200kPa40kPa-100kPa200kPa1.8MPa
400kPa80kPa-100kPa400kPa2.5MPa
1MPa200kPa-100kPa1MPa4MPa
2MPa400kPa-100kPa2MPa4MPa
4MPa800kPa-100kPa4MPa6MPa
7MPa1.4 MPa-100kPa7MPa10MPa
A10kPa2kPa0kPa10kPa400kPa
20kPa5kPa0kPa20kPa600kPa
50kPa10kPa0kPa50kPa600kPa
100kPa20kPa0kPa100kPa1MPa
200kPa40kPa0kPa200kPa1.8MPa
400kPa80kPa0kPa400kPa2.5MPa
1MPa200kPa0kPa1MPa4MPa
High and low limit setting requirements: lower range value (LRV) and upper range value (URV) must be set within the lower and upper range limits, |URV-LRV|≥ Minimum Range

Accuracy

Based on standards and reference test conditions, including best fit straight line (BFSL), hysteresis, repeatability. Calibration temperature :20 degrees C ±5 degrees C.
Linear Output AccuracyKTD<=5±0.2% Span<=35kPa
±0.1% Span≥800kPa
BTD<=5±0.2% Span<=100kPa
±0.1% Span≥200kPa
CTD<=5±0.2% Span<=20kPa
±0.1% Span≥50kPa
Note: TD (Turn down) means turndown ratio , TD= maximum range / current range

Ambient Temperature Influence

Sensor TypeInfluencing QuantityRange
K/C± (0.1+0.035TD) % 20 degrees C of  Span≥35kPa
B± (0.15+0.075TD) % 20 degrees C of  Span<=100kPa
± (0.15+0.055TD) % 20 degrees C of  Span≥200kPa

Environmental Conditions

ItemCondition
Operating Ambient Temperature Range-40 degrees C ~ 85 degrees C
Storage Ambient Temperature Range-40 degrees C ~ 100 degrees C
Measured Medium Temperature Range-20 degrees C ~ 70 degrees C
Operating Ambient Humidity Range5%RH~100%RH@40 degrees C
Hazardous AreaPCECCertificate No.: CE20.2148X

Ex ia IIC T6 Ga

Time Specifications

Total damping time constant: equals the sum of the electronic circuit component damping time constant and sensor capsule damping time constant
Overall response time: <= 90ms

Power Supply and Load Conditions

ItemOperating Condition
Power Supply VoltageHART communication protocol: 16.5V~36V DC
Modbus-RTU/RS485: 12V~36V DC
Load Resistance0Ω~2119Ω during operation

250Ω~600Ω for HART communication

Transmission Distance< 1000m
Power Consumption
4mA~20mA<= 500mW@24V DC, 20.8mA
Modbus-RTU/RS485<= 240mW@24V DC, 10mA

Related Products

Case Showcase

Frequently Asked Questions

Find quick answers about product selection, customization, technical parameters, delivery, and support for ADDA industrial measurement instruments.

官网询盘

Please provide the measured medium, measuring range, process temperature, process pressure, connection type, output signal, power supply, installation environment, and communication method if remote monitoring is required.

Yes. ADDA can provide customized solutions based on measuring range, process connection, wetted material, display type, communication protocol, installation method, and working environment.

Many ADDA instruments are available with explosion-proof or intrinsically safe configurations. Please confirm the site classification and certification requirements before selection.

Yes. Our team can help recommend a suitable instrument configuration after reviewing your application conditions, including medium, range, connection, output signal, and installation requirements.

Lead time depends on product type, quantity, customization requirements, and certification needs. Standard products usually have a shorter delivery time, while customized models may require additional production time.